Site 40.0 × 18.0 m; the floor plate is reworked to 40.0 × 16.00 m —
the north wall moves 1,250 south, widening the boundary clearance from 750 to 2.0 m,
so the footings and blinding sit well clear of the neighbour's land.
North eave 0 (internal gutter) · truss span 15.60 m ·
front run-off 1.45 m · rear run-off 0.75 m.
The 2.0 m gap gives erection crews comfortable working room, and it lets intake louvres run
the full length of the north face.
The bleachers have been deleted (item 9) — the north run-off is 750.
South wall: the existing shared wall with the academy is only 2,000 high,
so it is demolished and rebuilt (item 9) in the same precast wall T100 as the north.
Openings are cast at the plant, so there is no cutting work on site.
Main entrance W3,000 sits in the south wall of the glass block at x 33.6-36.6,
facing the academy gate.
RC columns 350×350 full height · 8-D20 main bars (PMC — the wall became a slab,
so the face load the column carries went down).
Abutting buildings: north x 0-15 (2 storeys) · south staff dormitory x 0-13
— everything beyond is open (items 1, 2). The east side toward the petrol station was
confirmed on site to be vacant ground (item 9).
The climbing wall is cancelled (item 3). The four east gable columns that were its
anchor line stay, because they now carry the gable wall and its precast panels.
Air intake (rebuilt per item 12 ①②⑤) — 8 north (the 2.0 m
clearance opens the whole north face) · 4 south low-level ·
3 large on the east gable = 15 locations, effective free area 11.4 m²,
plus a continuous intake L32.4 under the south eave.
The "no openings on the east" premise is withdrawn — the owner re-inspected the site
and confirmed it is open ground well clear of the petrol station. The 16.00 m east gable
sees outside air across its full width, and with the 2.0 m clearance the north face
now breathes as well (only the south stays blocked by the dormitory for 13 m).
Using almost all of the 5,000 / 5,550 / 3,300 clear bays between the C3 columns,
the openings are 4,400 + 4,950 + 2,700 × H1,090 (GL+1,160-2,250).
Court 1's end line is at x 1,500, so balls strike these directly — a
ball-guard grille ∅16 @100 is added.
The two west gable louvres are deleted (item 12 ②) — as the owner pointed out,
they opened not into the arena but into the lobby/stair (z 4,300) and the simulation
room (z 13,700). Air entering a closed room never reaches the court, so they added
nothing to ventilation while punching openings into the street facade.
Do gable louvres help ventilation? (item 12 ⑤) — Yes, but only low, and only
as intake. The ridge outlet is a 40 m × 1,000 cap with about 7.0 m² of free area,
while the previous 10 intakes at 1,880×680 with a 0.40 free ratio gave only 5.1 m² —
the exhaust was being throttled by the intake. With 8 north, 4 south and 3 east louvres
the intake now totals 11.4 m², comfortably above the 7.0 m² ridge outlet.
Louvres are not cut into the gable triangle (above the 8,000 eave) — an opening
that high sits above the neutral plane with the ridge, short-circuits the stack, and can
reverse-flow the ridge vent depending on wind direction.
Glass block, ground floor — lobby / performance space (8,300 open to the court) /
backstage store / simulation room. The party-wall column at z 8,800, removed to create
the performance space, is replaced by transfer beam TG1 H-600×200
(span 8,500 · point load 196 kN) (items 5, 6).
Five new west gable columns (item 11 — an omission the owner caught from the 3D).
Up to this point the columns on the west wall line (x 39,630) stopped at +3,550, under the
second-floor beam. Nothing carried the roof: the eave ring beam would have cantilevered
7.2 m past the last truss T4 (x 32,700) and the west gable frame would have hung in
mid-air. The east gable had four columns running to the roof; only the west was missing —
not a decision, an omission. They now run to the roof (same 350×350 section as the
other columns). They reuse the second-floor beam grid, so the foundation positions do
not change.
The second floor was raised 500, FL+3,700 → +4,200 (item 11) — with the stage at H500,
the old level left only 3,200 of headroom above it.
The stair is a straight flight of 24 risers, R175.0 × T280 · 32.0° · 2R+T=630 ·
width 1,250 · z 2,360→8,800, passing over the backstage store (items 7, 11).
Clear headroom under the beam at z 4,550 rises from 2,053 to 2,125, so the
headroom shortfall noted on the earlier drawings is resolved.
Stage H500 · 3,700 × 8,300 = 30.7 m² · 3 steps at the front.
From the stage deck to the underside of TG1 is 2,950.
Glass block, second floor — a single open room with no partitions, 103.3 m² ·
curtain wall FL+4,200 to +7,400.
Foundations — all concentric pad footings (items 8, 9). There is not one
eccentric footing. With the north clearance widened to 2,000, the excavation-limit problem
disappears and the F2 rectangular pads (1,800×1,300) are abolished — every column
sits on the same F1 1,500×1,500×T400. The north edge of the northmost pads lands at
z 16,350, leaving 1,650 clear of the boundary (1,550 including lean concrete).
The 39.4 m of SB1 strap beams is deleted in full.
Item 12 ⑧ — "the east and west columns stand 8 m alone; can there really be no
intermediate or upper beam?" Under the precast scheme the answer gets simpler. Two parts.
(1) The columns are restrained at the head and at mid-height.
The eave RC ring beam 300×400 runs the 40 m of both the south and north, the gable rake beams
tie the gable column heads up to the ridge, and roof-plane X-bracing in the end bays carries
those heads back to trusses T1 and T4. On top of that the B1 wall beams 200×340 come in two
tiers (GL+3,660-4,000 · 7,660-8,000) to carry the precast panels, and they give the column
an intermediate restraint. The free length drops from 9,100 to 3,660, so even at
350 square k·lu/r = 0.8×3,660 / (0.3×350) = 28, far below the braced limit of 40
(the previous scheme, 450 square over a free length of 9,100, was 54). With slenderness gone,
450×450 → 350×350 becomes possible, and the wall beam doubles as the intermediate RC beam.
(2) And the wind columns and girts disappear entirely.
The problem in the old scheme was never the column but the envelope — 75T PU panel spanned
5,450 vertically (GL+2,550 to the 8,000 eave) unsupported, while its allowable single
span at a 1.5 kPa design pressure was 4,000-4,500 (Cebu · NSCP 2015 Zone II V=200 km/h ·
partially enclosed GCpi ±0.55 → wall C&C 1.5-1.7 kPa). Wind columns and girts had to be
inserted to cut that span. Precast wall T100 spans the 3,660 between wall beams by itself,
so it needs nothing to back it up. With no panel left to support,
wind columns □-200×100×9 (-296,985 ₱) and
girts C-200×75×20×3.2 (-157,079 ₱) are deleted —
-454,064 ₱ in total, and structural steel drops from 18.8 to 15.3 tonnes.
The 75T panel survives only in the gable triangle, 33.44 m², where no wall beam can be
landed; there each tier is under 3,660, inside the allowable span.
Item 12 ⑨ electrical — the service entry and main distribution panel MDP sit
immediately to the right as you enter the store (inner face of the stage party wall,
x 36,350 · z 5,700). The riser climbs the party-wall line (x 32,700) to GL+7,800 under the eave;
the main tray runs along the south eave from T4 to T1 and then splits north-south along the
top face of the truss bottom chord (GL+7,860).
Socket outlets go only on the second floor (yoga/gym — treadmills) and in the simulation
room. Not one is placed in the arena court area — wall sockets get hit by balls and floor
sockets get soaked when the floor is washed.
Item 12 ③ The backstage store door D4 moves from
x 37,200-38,100 to 36,450-37,350, tight against the store/stage party wall and thus
850 further from the stair (x 38,200-39,450), so large items clear the treads more easily.
Item 12 ④ The single-storey south staff dormitory at H3,000 is now a
confirmed figure (previously "approx.").
Item 13 branding (signage · logo · brand colours) — switch "Branding" off in the left
panel and the building reverts exactly to its un-branded state. This is a proposal; compare
the two and decide.
(a) Roof signage south slope PHILINTER W27.0 · north slope ACADEMY W23.0,
folded white coated-steel letters. The two read in opposite directions — a sign on a
pitched plane must read from the side that plane faces, so on any single roof plan one of the
two is necessarily upside down. That is how the real building behaves.
(b) Entrance logo reproduced as supplied, on the second-floor south wall above the glass
door, centred at x 35,100 within x 33.6-36.6, baseline GL+5,300, overall
2,000 × 2,000, 40 mm relief. It sits above the 2,740 canopy and the 4,200 floor
and below the 8,000 eave, so nothing obstructs it from the front. The brush strokes are
genuinely raised solids, not a flat graphic, so they read as shadow.
"SINCE 2003" alone is small enough to become cut lettering in the working design.
The colour is dark green (#1f3b30) — the real logo colour the owner identified, and
since it is not among the white/red/blue brand colours it is kept as an
accent used on the logo only.
(c) White wall, blue lines The precast panels are plant-painted white (#e6e9e8), and
blue (#11479b) is laid only on lines that already exist — both bands are
the face of the B1 wall beam 200×340 itself. The eave band GL+7,660-8,000 is the upper
wall beam; the waist band GL+3,660-4,000 is the lower wall beam and also
the line where the precast panels divide into the lower and upper tier.
No new line is drawn; an existing line is made visible. A 200-wide band on each of the
four corners and a 250 band on the gable rake define the building outline.
A 150 red border is used on the main entrance only, so all three brand colours appear.
(d) NW Mondrian red, blue and yellow fields with a blue grid on the corner where the
west (street) and north faces meet. The owner picked the right place — west x 40,000 is
the street face and the only approach, the neighbour blocks the north for only x 0-15 so
x 32-40 is fully open, and the west gable became a completely blank wall once the
louvres were removed under item 12 ②.
The white wall is itself Mondrian's white ground, so only the colour fields and the grid
are added; painted area does not increase and the cost effect is negligible.
The grid is drawn in blue rather than the original's black, keeping it within the brand
colours. Note, however, that yellow is not one of the three brand colours — a version
using red and blue only is available if preferred.
Foundations — computed from the grid
computing…
Preparing view
Precast wall T100 — 1,200 wide panels, white finish (PMC)
18 mm panel joint — sealant both faces (PMC)
Insulated sandwich panel — gable triangle only (item 13)
Abutting buildings
0.5t coated-steel roof
Glass (curtain wall)
Sports PVC 3.5t
Steel truss · TG1 · RC columns 350×350 · B1 wall beam 200×340, 2 tiers
F1 pad footing 1,500×1,500×T400 — every location (F2 abolished by the 2.0 m clearance)
TB1 tie beam 250×400
Stage H500 (item 11)
Brand blue — outline and divider lines (item 13)
Brand red — entrance border, Mondrian (item 13)
Yellow — Mondrian only (outside the brand colours · item 13)
Logo dark green — raised entrance logo (item 13)